Features
Conductors use a strand that is able to provide excellent flexibility. In particular, 0.3 - 3.9 inches (8 - 100 mm) has been thinner wire diameter and improved softness.
JIS C 3316 Compliant
Conforms to the Electrical Safety Law (0.03 in (0.75 mm^2 - 100 mm^2) (0.5 mm^2 is not intended for electrical appliances)
[Conductor] Soft copper braid
Cable Color: Black
[Rated voltage] 600V
Rated Temperature: 140°F (60°C).
Structural Chart
[Conductor] Size (mm2) 0.9 inch (22 mm)
[Construction (pieces/pieces] 7/39/0.32 mm)
Outer Diameter: 0.2 inches (6.7 mm).
[Insulation Thickness (mm)] 1.6
[Finished outer diameter] 0.4 inches (9.9 mm)
Estimated Weight: 6.9 lbs (275 kg)
[Maximum conductor resistance (Ω/km-20°C)] 0.844
[Insulation Resistance]
MΩ·km 20℃ 40
140°F (60°C) 0.1
Test Voltage: 2000 V/ 1 minute (Submersible AC)
[Allowed Current (A)] 115
[Standard chief] 100 m
Allowed Current
Ambient temperature 30°C, allowable current value when setting 1 position in the air.
If the ambient temperature exceeds 30°C, multiply the following compensation factor.
Current reduction coefficient (when ambient temperature), Ambient temperature (℃) 30 Correction coefficient 1.00
Ambient Temperature (℃): 35 Correction Factor: 0.91
Ambient Temperature: 104°F (40°C), Correction Factor: 0.82
Ambient Temperature (℃) 45 Correction Coefficient 0.71
Ambient Temperature (℃): 50 Correction Factor: 0.58
Ambient Temperature (℃): 21.3 inches (55 cm), Correction Factor: 0.41
Current Reduction Coefficient (For Multi-Purpose Construction) Wire Coefficient 2-3 Current Reduction Coefficient 0.70 Wire Coefficient 4 Current Reduction Coefficient 0.70 Wire Coefficient 5-6 Current Reduction Coefficient 0.70 Wire Coefficient 2-3 Current Reduction Coefficient 0.70 Wire Coefficient 2-3 Current Reduction Coefficient 0 .70